當前位置:首頁 >> 資料下載 >> 三菱 >> FX系列PLC >> 三菱 FX1N 三菱-FX1N-BAT 用戶 手冊
三菱 FX1N 三菱-FX1N-BAT 用戶 手冊
所屬類別:三菱 >> FX系列PLC
資料介紹:

• The module case is made of resin; do not drop it or subject it to strong
shock.
Doing so may damage the module.
• When disposing of this product, treat it as industrial waste.
• When the FX1N-BAT is transported attached to a PLC and the life cycle
has passed or the BATT.V LED turns ON when the PLC is powered, the
data backed up by the capacitor will have become random.
Check the following two points before transporting the installed FX1N-
BAT attached to the FX1N series PLC.
- Life cycle of FX1N-BAT
- "BATT.V" LED of FX1N-BAT is OFF when the FX1N series PLC is
powered up.
• During transportation avoid any impact as the PLC is a precision
instrument.
It is necessary to check the operation of PLC after transportation, in case
of any impact damage.
• During transportation avoid any impact to the battery (FX1N-BAT) as the
PLC may be seriously damaged by liquid leakage etc. from the battery.
Standard
Please consult with Mitsubishi Electric for applicable standards.
1. Introduction
1.1 Introduction
The FX1N-BAT Battery Unit (hereinafter referred to as the FX1N-BAT) is installed on the
FX1N PLC to ensure that the capacitor-backed devices and clock data do not become
random values when power is not supplied to the PLC for a long time (10 days or more)
during transportation, etc.
The FX1N-BAT should be used within its expiration date (life cycle: 2 years at 25°C).
1.1.1 Dimensions and Each Part Name
Unit: mm (inches)
Accessory: Top cover for FX1N-BAT × 1, M3 screw to fix top cover × 1
1.1.2 Lot Number
1.2 System Configuration
One FX1N-BAT can be installed on an FX1N series main unit.
(FX1N-BAT cannot be installed on an FX1S series main unit.)
The FX1N-BAT can be used with an expansion board. See the following table for
possible configurations.
2. Specifications
Expansion Board / Display Module / Memory Cassette
Using with FX1N-232-BD, FX1N-422-BD,FX1N-485-BD, FX1N-CNV-BD,
FX1N-8AV-BD, FX1N-4EX-BD, FX1N-2EYT-BD
Not using with FX1N-2AD-BD, FX1N-1DA-BD, FX1N-5DM, FX1N-EEPROM-8L
40 (1.58")
32(1.26") 11.3
(0.45") 1)
2)
3)
4)
3)
1) BATT.V LED
2) Hook for fixation
3) Connector for PLC
4) Product name and Lot number
FX1N-BAT LOT.77 3VDC
FX1N-BAT
LOT.77
Production month: 1-9 = Jan. - Sept.,
X = Oct., Y = Nov., Z = Dec.
Production year: e.g. 5 = 2005, 7 = 2007
3.1 When not used with an expansion board
1) Turn Off the power to the PLC.
2) Remove the top cover of the PLC.
3) Attach the top cover (A) of the
FX1N-BAT accessory.
4) Secure the top cover (A) to the PLC
with a screw (B).
The screw should be tightened with
a torque of 0.3 to 0.6 N•m. The
screw must be secured to prevent
malfunction due to a loose
connection.
5) Fix the FX1N-BAT to connector (C)
on the PLC.
6) Turn On the power to the PLC.
3.2 When used with an expansion board
For installation of the expansion board,
refer to the FX1N Hardware Manual.
1) Turn Off the power to the PLC.
2) Remove the top cover of the
expansion board.
3) Remove section (A) with wire-
cutters to expose the connector.
4) Attach the top cover of the
expansion board.
5) Secure the top cover to the PLC
with screw (B).
The screw should be tightened with
a torque of 0.3 to 0.6 N•m. The
screw must be secured to prevent
malfunction due to a loose
connection.
6) Fix the FX1N-BAT to connector (C)
on the expansion board.
7) Turn On the power to the PLC.
4. Maintenance
4.1 Detecting Low voltage in the FX1N-BAT
The "BATT.V" LED of the FX1N-BAT lights when the low voltage is detected on power-
up of the FX1N series PLC. It is possible to output the status of the "BATT.V" LED to an
output terminal on the PLC with the following programs. Move Kœœœ into D8159 to
enable M(œœœ+4) to turn ON when the FX1N-BAT voltage becomes low. Note that
Mœœœ-M(œœœ+15) are also occupied for the low voltage detection. Therefore, these
devices should not be used for other applications.
4.2 Operation After Detecting Low Voltage in the FX1N-BAT
The "BATT.V" LED of FX1N-BAT lights when low voltage is detected on power-up of the
FX1N series PLC. Ten days after the "BATT.V" LED lights, the capacitor inside the PLC
will begin to back up the devices with whatever charge was present at the last power
down of the PLC. It is necessary to power-up the PLC every ten days, for a period of 30
minutes, to recharge the capacitor after the FX1N-BAT is no longer backing up the
devices. If power is not supplied for ten days or more, the capacitor-backed data will
become random. Further information concerning the capacitor backup can be found in
FX1N Hardware Manual.
4.3 Exchange Procedure
(A)
(B)
(C)
(A)
(B)
(C)
M8002
MOV K0 D8159
M4
Y0
Moving K0 into D8159 will occupy the
flags, M0 to M15, for detecting low
voltage in the FX1N-BAT.
When the FX1N-BAT experiences low
voltage, M4 is turned ON.
立即下載     
相關下載
主站蜘蛛池模板: 成人一级黄色大片 | 亚洲国产精品一区 | 精品亚洲综合 | 视频一区二区国产 | 一级性色 | 永久免费在线观看av | av在线免费观看网站 | 91久久精品国产亚洲 | 欧美精品久久久久久久久老牛影院 | 91精品国产九九九久久久亚洲 | 噜噜噜在线 | 亚洲欧美国产视频 | 欧洲黄色一级视频 | 一级做受毛片免费大片 | 久久亚洲国产精品 | 牛牛视频在线 | a一级黄 | 亚洲精品午夜在线 | av在线网站观看 | av电影免费在线看 | 嫩草影院在线观看网站成人 | 性少妇videosexfreexxx片 | 国产一级免费片 | 综合在线一区 | 日韩中文字幕一区二区三区 | 热re91久久精品国产99热 | 91精品国产乱码久久久久 | 欧美性生活久久久 | 国产午夜精品一区二区三区四区 | 日本在线观看视频网站 | 国产超碰人人做人人爱ⅴa 国产精品久久久久久久hd | 91av爱爱 | 精品一区二区三区在线观看视频 | 欧美日性 | 黄色片网站免费观看 | 蜜桃久久一区二区三区 | 免费看欧美黑人毛片 | 日韩在线欧美在线 | 黄色电影免费提供 | 丰满年轻岳中文字幕一区二区 | 手机国产乱子伦精品视频 |